CDVS96 / GR9S96 / VR9S96 seriesGoodman E1E fault code (CDVS96 / GR9S96 / VR9S96)

APS pressure error

What the manual says

APS pressure error

Models and series

Listed for: CDVS96, GR9S96, VR9S96.

Source

Service Manual RS6612302, p. 33

Symptom | LED
Status | Fault Description | Corrective Actions
Furnace fails to
operate | E1d | APS span error | Check Red, Black, White harness & connections to
inducer & control board
Check pressure hoses to pressure sensor and pressure
switch
Furnace fails to
operate | E1E | APS pressure error | Check Red, Black, White harness & connections to
inducer & control board
Replace pressure sensor
Furnace fails to
operate | E1F | APS input error | Check Red, Black, White harness & connections to
inducer & control board
Replace pressure sensor
Twinning feature not
working | EEH | TWIN Error | Check for wiring connections.
Replace integrated control board
Furnace fails to
operate and goes
to hard lockout | EbL | Main blower motor is consuming
very little current after heat on
delay, below an expected value | Check for loose motor wiring connections.
Verify if the blower motor is burnt, replace
blower motor if found burnt
Furnace fails to
operate and goes
to hard lockout | EbU | Main blower motor is consuming
too much current during inducer
pre-purge, above an expected
value. | Verify wiring connections to and from motor
are not loose.
Verify that line voltage wires to the control
and the main blower motor are not reversed
at the control.
Furnace fails to
operate | Ed0 | No Shared data | Populate shared data set using BTPIM01
Furnace stops heating
and only the fan is
operating | EAF | Furnace has lost communication with the
R-32 sensor and the furnace is in
mitigation mode. | Verify wire connection to R-32 sensor is not loose.
Verify that the R-32 sensor wire is not damaged.
Replace R-32 Sensor.
Furnace stops heating
and only the fan is
operating | EAL | R-32 sensor has detected a refrigerant
leak and furnace is in mitigation mode. | Investigate the indoor coil for a refrigerant leak.
Furnace will resume normal operation once a leak is not
detected and the 5 minute delay period is over.
Furnace stops heating
and only the fan is
operating | EAS | R-32 sensor has detected a fault and the
furnace is in mitigation mode. | Investigate the R-32 sensor.
Replace the R-32 sensor.
Furnace stops heating
and only the fan is
operating | Ear | A2L relay in the furnace control board
has detected a fault and the furnace is in
mitigation mode. | Investigate A2L relay.
Cycle power on the furnace.
Replace integrated control board.
Furnace fails to
operate.
Integrated control
module LED display
provides no signal | None | No 115 power to furnace or no 24 volt
power to integrated control module.
Blown fuse or tripped circuit breaker
Integrated control module is non-
functional | Restore high voltage power to furnace and integrated
control module.
Correct condition which caused fuse to open, replace
fuse
Replace non-functional integrated control module.

Other Goodman codes in this family

Ask about your unit

Last checked 2026-11-18 against Service Manual RS6612302.

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.