CDVS96 / GR9S96 / VR9S96 seriesGoodman E1d fault code (CDVS96 / GR9S96 / VR9S96)

Analog Pressure Sensor Span Error. Inconsistent pressure reading with inducer ON

What the manual says

Analog Pressure Sensor Span Error. Inconsistent pressure reading with inducer ON

Models and series

Listed for: CDVS96, GR9S96, VR9S96.

Source

Service Manual RS6612019, p. 31

Symptom | LED Status | Fault Description | Corrective Actions
Furnace operates at reduced
performance or operates on
low stage when high stage is
expected | E | Airflow is lower than demanded | Check filters for blockage, clean filters or remove
obstruction
Check ductwork for blockage, remove
obstruction and verify all registers are fully open
Verify ductwork is appropriately sized for system,
resize and/or replace ductwork if necessary
Furnace fails to operate | E1 | Analog Pressure Sensor
Reference Error. APS reference
is out of the range (5.0+/-0.2)V
for 5 seconds | Verify electrical connections to pressure sensor
Furnace fails to operate | E1 | Analog Pressure Sensor Null
Error. Inconsistent Pressure
reading with inducer OFF | Verify electrical connections to pressure sensor
Furnace fails to operate | E1d | Analog Pressure Sensor Span
Error. Inconsistent pressure
reading with inducer ON | Verify electrical connections to pressure sensor
Furnace fails to operate | E1 | Analog Pressure Error (Blocked
Vent Error) | Need to check the APS Sensor or its connection
if this error is occurred. The failure conditions
occur as per the following for 5 seconds:
1. The vent is blocked, and the pressure could not
reach (lower than)
the target pressure when inducer stayed at
maximum RPM which
stored in Shared Data.
2. The vent is blocked, and the pressure could not
reach (higher than)
the target pressure when inducer stays at the
minimum RPM
(Pressure Switch Min Limit).
3. APS fault causes the pressure fixed at a value
lower than the target
pressure when inducer stayed at maximum RPM
which stored in
Shared Data.
4. APS fault causes the pressure fixed at a value
higher than the target
pressure when inducer stayed at minimum RPM
(Pressure Switch
Min Limit).
Furnace fails to Operate | E1 | Analog Pressure Sensor, Input
Error | Check the APS Sensor or its connection if this
error is occurred. APS input voltage is out of the
below ranges for 5 seconds.
1. If 2" is selected, the voltage range shall be from
(0.25-0.06)V to (4+0.06)V.
2. If 4" is selected, the voltage range shall be from
(0.5-0.06)V to (4.5+0.06)V.

Other Goodman codes in this family

Ask about your unit

Last checked 2026-11-18 against Service Manual RS6612019.

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.