System Alert Guide 529992050Trane SOP.004.54 fault code

DISCHARGE TEMP SENSOR LOCKOUT

What the manual says

DISCHARGE TEMP SENSOR LOCKOUT

Source

System Alert Guide 529992050, p. 51

SOP.004.54
 | DISCHARGE TEMP
SENSOR LOCKOUT | "The Discharge Temperature
Sensor has tripped 4 times
within one hour
- Cycle system power to reset" | Low or no airflow
Faulty damper(s) or dampers wired backwards
Incorrect zone airflow size
Heating/cooling equipment not operating correctly
Low/high supply air temperature due to low
ambient cooling or high ambient heating
Verify airflow mode is set to Constant CFM not
Constant Torque and the CFM/ton is set to 400

Other Trane codes in this family

Ask about your unit

Last checked 2026-11-18 against System Alert Guide 529992050.

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.