DIFFERENTIAL STATIC PRESS SENSOR FAULT

What the manual says

DIFFERENTIAL STATIC PRESS SENSOR FAULT

Source

System Alert Guide 529992050, p. 50

SOP.004.51
 | DIFFERENTIAL STATIC
PRESS SENSOR
FAULT | Differential Static Press Sensor
Fault | No static pressure sensor installed
Pressure transducer tubing has been reversed
The static pressure exceeds the operating range of
the sensor (greater than 2""w.c.)
Sensor is open or shorted
- 4.99vDC = Open sensor
- 0vDC = Shorted sensor
No source voltage to sensor
- With sensor disconnected, 5vDC should be
Ask about your unit