EL296D / EL297D / ML296D / ML296U / ML297D / ML297U seriesLennox E311 fault code (EL296D / EL297D / ML296D / ML296U / ML297D / ML297U)
Heat rate reduced to match indoor blower air flow.
What the manual says
Heat rate reduced to match indoor blower air flow.
Models and series
Listed for: EL296D, EL297D, ML296D, ML296U, ML297D, ML297U.
Checks from the manual
- Warning Only. Furnace blower in cutback mode due to restricted airflow. Reduce firing rate every 60 seconds to match available CFM. Check filter and duct system. To clear, replace filter if needed or repair/ add duct. 2-stage controls will reduce firing rate to 1st stage. Clears when heat call finishes successfully.
Source
EL296DFV Downflow Variable Communicating Service, p. 18
E311 | Heat rate reduced to match indoor blower air flow. | Warning Only. Furnace blower in cutback mode due to restricted airflow. Reduce firing rate every 60 seconds to match available CFM. Check filter and duct system. To clear, replace filter if needed or repair/ add duct. 2-stage controls will reduce firing rate to 1st stage. Clears when heat call finishes successfully.