RESI-GF-A93DF1EK-92G1DFEK-DOWNFLOW-INSTALLATIONMANUALArmstrong Air E155 fault code
Refrigerant Leak Detector Sensor #2 Communication lost
What the manual says
Refrigerant Leak Detector Sensor #2 Communication lost
Checks from the manual
- There may be an issue with the wiring harness connecting the sensor #2 to the furnace control board, either with the wiring itself or with the connector. Check the wiring and the connector for damage or improper connectivity. Check the sensor for damage or obstruction on the harness plug. This fault clears when communications with the sensor has been reestablished, but blower latches for a minimum of 5 minutes. Retest of the presence of fault can be effected by pressing the Low GWP test button on the furnace unit control board
Source
RESI-GF-A93DF1EK-92G1DFEK-DOWNFLOW-INSTALLATIONMANUAL, p. 43
E155 | Refrigerant Leak Detector Sensor #2 Communication lost | There may be an issue with the wiring harness connecting the sensor #2 to the furnace control board, either with the wiring itself or with the connector. Check the wiring and the connector for damage or improper connectivity. Check the sensor for damage or obstruction on the harness plug. This fault clears when communications with the sensor has been reestablished, but blower latches for a minimum of 5 minutes. Retest of the presence of fault can be effected by pressing the Low GWP test button on the furnace unit control board
Other Armstrong Air codes in this family
Ask about your unit
Last checked 2026-11-18 against RESI-GF-A93DF1EK-92G1DFEK-DOWNFLOW-INSTALLATIONMANUAL.
Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.