Low 24V - Control will restart if the error recovers.

What the manual says

Low 24V - Control will restart if the error recovers.

Checks from the manual

  1. 24-Volt Power Low (Range is 18 to 30 volts). Check and correct voltage. Check for additional power-robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace / air handler. Clears after fault recovered.

Source

RESI-GF-A93DF1EK-92G1DFEK-DOWNFLOW-INSTALLATIONMANUAL, p. 42

E115 | Low 24V - Control will restart if the error
recovers. | 24-Volt Power Low (Range is 18 to 30 volts). Check and correct voltage.
Check for additional power-robbing equipment connected to system.
May require installation of larger VA transformer to be installed in
furnace / air handler. Clears after fault recovered.