Installation Manual: R-454B Outdoor Split-System Single-Phase Variable Speed Heat Pump - YH9 and XH9 SeriesYork 32 fault code

INV: AC INPUT OVER CURRENT

What the manual says

INV: AC INPUT OVER CURRENT

Checks from the manual

  1. See causes from error 26 "INV: COMP OVER CURRENT" | | | Reduced input voltage | Check the line voltage if it is < 187 VAC. | | Distorted input voltage | Check the line voltage for noise. Call an electrician or the power company if noise is found. | | High compressor load | Check the compressor is operating with in specified limits. | | Faulty inverter drive | Change out the inverter drive. (Validate the fix. If the issue is persistent, reinstall the original inverter drive.) | | If fault remains. | Contact Technical Services.

Source

Installation Manual: R-454B Outdoor Split-System Single-Phase Variable Speed Heat Pump - YH9 and XH9 Series, p. 61

32 | INV: AC INPUT OVER CURRENT | See causes from error 26 "INV: COMP OVER CURRENT" | 
 |  | Reduced input voltage | Check the line voltage if it is < 187 VAC.
 |  | Distorted input voltage | Check the line voltage for noise. Call an electrician or
the power company if noise is found.
 |  | High compressor load | Check the compressor is operating with in specified
limits.
 |  | Faulty inverter drive | Change out the inverter drive. (Validate the fix. If the
issue is persistent, reinstall the original inverter drive.)
 |  | If fault remains. | Contact Technical Services.