Installation Manual: R-454B Outdoor Split-System Single-Phase Variable Speed Heat Pump - YH9 and XH9 SeriesYork 32 fault code
INV: AC INPUT OVER CURRENT
What the manual says
INV: AC INPUT OVER CURRENT
Checks from the manual
- See causes from error 26 "INV: COMP OVER CURRENT" | | | Reduced input voltage | Check the line voltage if it is < 187 VAC. | | Distorted input voltage | Check the line voltage for noise. Call an electrician or the power company if noise is found. | | High compressor load | Check the compressor is operating with in specified limits. | | Faulty inverter drive | Change out the inverter drive. (Validate the fix. If the issue is persistent, reinstall the original inverter drive.) | | If fault remains. | Contact Technical Services.
Source
Installation Manual: R-454B Outdoor Split-System Single-Phase Variable Speed Heat Pump - YH9 and XH9 Series, p. 61
32 | INV: AC INPUT OVER CURRENT | See causes from error 26 "INV: COMP OVER CURRENT" | | | Reduced input voltage | Check the line voltage if it is < 187 VAC. | | Distorted input voltage | Check the line voltage for noise. Call an electrician or the power company if noise is found. | | High compressor load | Check the compressor is operating with in specified limits. | | Faulty inverter drive | Change out the inverter drive. (Validate the fix. If the issue is persistent, reinstall the original inverter drive.) | | If fault remains. | Contact Technical Services.
Ask about your unit
Last checked 2026-11-18 against Installation Manual: R-454B Outdoor Split-System Single-Phase Variable Speed Heat Pump - YH9 and XH9 Series.
Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.