System Alert Guide 529992050Trane ERR.184.01 fault code
COMPRESSOR DOME TEMPERATURE PROTECTION - HIGH SPEED
What the manual says
COMPRESSOR DOME TEMPERATURE PROTECTION - HIGH SPEED
Source
System Alert Guide 529992050, p. 41
ERR.184.01 | COMPRESSOR DOME TEMPERATURE PROTECTION - HIGH SPEED | Compressor high temperature protection at high speed (15 minute soft lockout) 5 occurrences within approx. 5 hours will result in Universal Hard Lockout (184.08) | Low charge Restricted metering device. Check for high superheat. - Indoor expansion valve in cooling mode - Outdoor expansion valve in heating mode Restricted condenser airflow in cooling mode Check dome temperature sensor calibration High indoor ambient in heat mode (Indoor set point above 80F). - Increase ID airflow
Ask about your unit
Last checked 2026-11-18 against System Alert Guide 529992050.