System Alert Guide 529992050Trane ERR.166.00 fault code

LOW SUPERHEAT OCCURRENCES COOLING

What the manual says

LOW SUPERHEAT OCCURRENCES COOLING

Source

System Alert Guide 529992050, p. 31

ERR.166.00
 | LOW SUPERHEAT
OCCURRENCES
COOLING | Indoor EEV motor is at the
minimum position but superheat
remains less than 3 degrees for
20 continual minutes of cooling
operation
Multiple cycles with low superheat
will result in a system lockout
Cycle power to reset | EEV motor not seated properly on the valve
ET or GT sensor is out of calibration
- Check resistance or voltage per Service Facts
External check valve leaking (Not all models have external
check valve)
Possible stuck valve (EEV)
- Run EEV open/close test from CDA
Restricted circuit where ET sensor is located
- Perform coil frost test by running the system with the air
handler coil door removed to check for frost
Ask about your unit

Last checked 2026-11-18 against System Alert Guide 529992050.

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.