System Alert Guide 529992050Trane ERR.166.00 fault code
LOW SUPERHEAT OCCURRENCES COOLING
What the manual says
LOW SUPERHEAT OCCURRENCES COOLING
Source
System Alert Guide 529992050, p. 31
ERR.166.00 | LOW SUPERHEAT OCCURRENCES COOLING | Indoor EEV motor is at the minimum position but superheat remains less than 3 degrees for 20 continual minutes of cooling operation Multiple cycles with low superheat will result in a system lockout Cycle power to reset | EEV motor not seated properly on the valve ET or GT sensor is out of calibration - Check resistance or voltage per Service Facts External check valve leaking (Not all models have external check valve) Possible stuck valve (EEV) - Run EEV open/close test from CDA Restricted circuit where ET sensor is located - Perform coil frost test by running the system with the air handler coil door removed to check for frost