System Alert Guide 529992050Trane ERR.123.00 fault code
ELECTRIC HEAT CONFIGURATION FAULT
What the manual says
ELECTRIC HEAT CONFIGURATION FAULT
Source
System Alert Guide 529992050, p. 25
ERR.123.00 | ELECTRIC HEAT CONFIGURATION FAULT | Number of electric heat stages originally discovered by the heat detection circuit is different than the number of heat stages reporting | TAM9 / TEM8 Indoor Units - Electric heat is configured in the thermostat but not in the airflow control (AFC) and the thermostat has an active call for electric heat. Configure TAM9/TEM8 airflow control (AFC) for correct electric heat size (kw) selected from the CDA or 7-segment on the AFC control. - Electric heat is configured in the thermostat for more stages than what is configured in the airflow control (AFC) and the thermostat has an active call for electric heat. Verify the number of electric heat stages in the thermostat matches the configured electric heat size (kw) selected from the CDA or 7-segment on the AFC control. TAM8 / AAM8 Indoor Units - This error cannot occur unless a new unprogrammed EHC has been installed and the KW jumper position is on PARK. Set KW jumper to match the model number CLII / AccuLink Units Only - Open TCO or heater contactor circuit Number of electric heat banks has changed since start-up