System Alert Guide 529992050Trane ERR.123.00 fault code

ELECTRIC HEAT CONFIGURATION FAULT

What the manual says

ELECTRIC HEAT CONFIGURATION FAULT

Source

System Alert Guide 529992050, p. 25

ERR.123.00
 | ELECTRIC HEAT
CONFIGURATION
FAULT | Number of electric heat stages
originally discovered by the heat
detection circuit is different
than the number of heat stages
reporting | TAM9 / TEM8 Indoor Units
- Electric heat is configured in the thermostat but not in
the airflow control (AFC) and the thermostat has an active
call for electric heat. Configure TAM9/TEM8 airflow control
(AFC) for correct electric heat size (kw) selected from the
CDA or 7-segment on the AFC control.
- Electric heat is configured in the thermostat for more
stages than what is configured in the airflow control (AFC)
and the thermostat has an active call for electric heat.
Verify the number of electric heat stages in the thermostat
matches the configured electric heat size (kw) selected
from the CDA or 7-segment on the AFC control.
TAM8 / AAM8 Indoor Units
- This error cannot occur unless a new unprogrammed EHC
has been installed and the KW jumper position is on PARK.
Set KW jumper to match the model number
CLII / AccuLink Units Only
- Open TCO or heater contactor circuit
Number of electric heat banks has changed since start-up

Other Trane codes in this family

Ask about your unit

Last checked 2026-11-18 against System Alert Guide 529992050.

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.