System Alert Guide 529992050Trane ERR.114.01 fault code
PERSONALITY MODULE COMPRESSOR SIZE MISMATCH
What the manual says
PERSONALITY MODULE COMPRESSOR SIZE MISMATCH
Source
System Alert Guide 529992050, p. 23
ERR.114.01 | PERSONALITY MODULE COMPRESSOR SIZE MISMATCH | Outdoor unit tonnage stored in outdoor unit Personality Module (PM) does not match capacity range in indoor Personality Module (PM) System will continue to operate with this error but a fault will be displayed on user interface | Outdoor unit is not a rated match with indoor unit See AHRI Ratings for proper system match-ups
Ask about your unit
Last checked 2026-11-18 against System Alert Guide 529992050.
Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.