What the manual says
DEFROST FAULT B AND/OR C
Source
System Alert Guide 529992050, p. 15
ERR.068.01 | DEFROST FAULT B AND/OR C | Defrost Fault B and/or C Very high delta T Defrost terminated at least 10 times in a row on maximum override time (15 minutes) instead of temperature | Open outdoor coil sensor Shorted outdoor ambient air sensor Low refrigerant charge Outdoor TXV not controlling properly SOV stuck in heating mode Outdoor fan failure or Outdoor fan running during defrost