DEFROST FAULT B AND/OR C

What the manual says

DEFROST FAULT B AND/OR C

Source

System Alert Guide 529992050, p. 15

ERR.068.01
 | DEFROST FAULT B
AND/OR C | Defrost Fault B and/or C
Very high delta T
Defrost terminated at least
10 times in a row on maximum
override time (15 minutes) instead
of temperature | Open outdoor coil sensor
Shorted outdoor ambient air sensor
Low refrigerant charge
Outdoor TXV not controlling properly
SOV stuck in heating mode
Outdoor fan failure or Outdoor fan running during defrost