Skip to content

System Alert Guide 529992050Trane ERR.067.04 fault code

DOME TEMPERATURE SENSOR FAULT COOLING

What the manual says

DOME TEMPERATURE SENSOR FAULT COOLING

Source

System Alert Guide 529992050, p. 14

ERR.067.04
 | DOME TEMPERATURE
SENSOR FAULT
COOLING | Compressor temperature sensor is
faulted in cooling mode
Depending on compressor type;
the sensor may be located on top
of compressor dome or discharge
line | Dome temp sensor open or shorted
Zero or infni ite resistance
Dome temp sensor out of range
Compare resistance value of sensor to chart in literature
No output voltage from control board to sensor
A reading between 3vDC and 5vDC with the sensor removed
confri ms a good source voltage