Upflow/Horizontal and Dedicated Downflow Gas-Fired, Direct/Non-Direct Vent, Modulating Condensing Variable Speed Furnaces with Variable Speed Draft InducerTrane E2.1 fault code

Retries Exceeded - 1 hour lockout

What the manual says

Retries Exceeded - 1 hour lockout

Source

Upflow/Horizontal and Dedicated Downflow Gas-Fired, Direct/Non-Direct Vent, Modulating Condensing Variable Speed Furnaces with Variable Speed Draft Inducer, p. 104

Alarm | Alarm Explanation | Error
Code | Comm
Code | P2
Priority | Possible Causes
Internal Failure
Error | Loss of the IRQ or other
internal failures | E01 | ERR.018.00 | Critical | Replace indoor control board. Board failure could be caused by line
voltage spikes or electrostatic discharge.
External Lockout | Retries Exceeded - 1
hour lockout | E2.1 | ERR.022.01 | Critical | Flame sensor not sensing flame. Flame current is less than 1 micro
amp. Flame sensor not positioned properly in flame. Inlet gas
pressure too low. Outlet gas pressure too low. Burner crossovers not
aligned properly or restricted.
 | Recycles Exceeded - 1
hour lockout | E2.2 | ERR.022.00 | Critical | Gas valve solenoid failing. Inlet gas pressure dropping too low. Air
impingement on burners or flame. Debris in gas valve screen or
blockage in supply line. Gas pressure regulator failing.
 | 1st Stage Gas Valve Not
energized When It
Should Be (After 10
Times) | E2.3 | ERR.022.02 | Critical | Verify all wiring is connected, correct and intact. Replace the IFC.
 | General Gas Valve
Lockout | E2.4 | ERR.022.03 | Critical | Gas valve may be bad. Cycle furnace power and retry. Replace gas
valve, then IFC if problem persists.