Skip to content

Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.186.00 fault code

Protection derating fault

What the manual says

Protection derating fault

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 12

CL2.186.00 | Normal | MCP HD | Protection derating fault | High Drive output current, Limit
compressor speed | High compressor load |  | 
CL2.186.01 | Normal | MCP DN | Protection derating fault | High Drive output current, Derate
compressor speed | High compressor load |  | 
CL2.186.02 | Normal | MTP HD | Protection derating fault | High Inverter temperature, Limit
compressor speed | High compressor load |  | 
CL2.186.03 | Normal | MTP DN | Protection derating fault | High Inverter temperature, Derate
compressor speed | High compressor load |  | 
CL2.186.04 | Normal | RTP HD | Protection derating fault | High Rectifier temperature, Limit
compressor speed | High compressor load |  | 
CL2.186.05 | Normal | RTP DN | Protection derating fault | High Rectifier temperature, Derate
compressor speed | High compressor load |  | 
CL2.187.00 | Critical | Evacuation | Evacuation mode | Evacuation mode has been executed
from the CDA. ODU operation is locked
out and EEV drives to full open. | Evacuation mode has been executed from the CDA |  | 
CL2.187.01 | Critical | DRV Test | Drive diagnostics mode | Drive Diagnostics Test is in progress | Technician to determine after running the diagnostic
test. See CDA Technicians Control menu. This
information will be required for warranty replacement
part credit. |  | 
CL2.188.00 | Critical | STR LOAD F | Storage load failure | Internal Error | Cycle power and see if alert clears
**Call for tech support, record failure mode for warranty
claim before replacing Drive |  | 
CL2.188.01 | Critical | STR UPD F | Storage update failure | Internal Error | Cycle power and see if alert clears
**Call for tech support, record failure mode for warranty
claim before replacing Drive |  | 
CL2.188.02 | Critical | STATE ERR | State failure | Internal Error | Cycle power and see if alert clears
**Call for tech support, record failure mode for warranty
claim before replacing Drive |  | 
CL2.188.03 | Critical | HW VAR RD F | Hardware variant read | Internal Error | Cycle power and see if alert clears
**Call for tech support, record failure mode for warranty
claim before replacing Drive |  | 
CL2.188.04 | Critical | APP EXCP | Application exception | Internal Error | Cycle power and see if alert clears
**Call for tech support, record failure mode for warranty
claim before replacing Drive |  |
Ask about your unit

Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.