Protection derating fault

What the manual says

Protection derating fault

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 12

CL2.185.07 | Normal | MCLP HD | Protection derating fault | Low compressor speed with high Drive
output current, Limit compressor speed | Low speed with high condenser load.
(Indoor coil in heating mode/outdoor coil in cooling
mode) |  | 
CL2.185.08 | Normal | CLG DERATE | Protection derating fault | Indoor coil freeze protection is active,
Derate compressor speed | In cooling mode: low load, indoor/outdoor low ambient
operation.
Low airflow, low humidty, Low RH dehumidification
target. |  | 
CL2.185.09 |  | SYS OR | Protection derating fault | System Oil Return function active to
bring oil back to compressor | Low Dome temperature with an ON cycle and/or
multiple short cycles. |  | 
CL2.185.10 | Normal | LSPP CLG DN | Protection derating fault | Low Suction Pressure Protection in
cooling mode, Derate compressor speed | In cooling mode: low indoor/outdoor ambient operation. |  | 
CL2.185.11 | Normal | LSPP CLG HD | Protection derating fault | Low Suction Pressure Protection in
cooling mode, Limit compressor speed | In cooling mode: low indoor/outdoor ambient operation. |  | 
CL2.185.12 | Normal | LSPP HTG DN | Protection derating fault | Low Suction Pressure Protection in
heating mode, Derate compressor speed | In heating mode: low outdoor ambient/indoor
temperature operation. |  | 
CL2.185.13 | Normal | LSPP HTG HD | Protection derating fault | Low Suction Pressure Protection in
heating mode, Limit compressor speed | In heating mode: low outdoor ambient/indoor
temperature operation. |  | 
CL2.185.14 | Normal | DIAGCUR DN | Protection derating fault | High compressor speed with high Drive
output current, Derate compressor