Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.180.00 fault code

Supply voltage failure

What the manual says

Supply voltage failure

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 10

CL2.180.00 | Normal | HI PWR DER | Supply voltage failure | Low supply voltage and/or high power
output from Drive -compressor running
at a reduced RPM (Derate) | Maximum power is reduced with line voltage less than
200VAC.
High load conditions
- Recirculation
- Dirty coils
- Low airflow |  | 
CL2.180.02 | Major | LOW VOLT CO | Supply voltage failure | Supply voltage is less than 175VAC | Supply voltage is less than 175VAC |  | 
CL2.180.03 | Normal | HGH PWR CO | Supply voltage failure | Drive output current exceeds internal
limit set for current sensor | High load condition
- Recirculation
- Dirty coils
- Low airflow
Drive hardware failure (Run Drive Diagnostics) |  | 
CL2.181.00 | Major | GATE DRV CO | Gate drive failure | Drive hardware failure alert | Drive hardware failure. 10 consecutive occurrences will
result in an Err 181.07 |  | 
CL2.181.01 | Normal | REV ROT CO | Reverse rotation
protection soft lockout | Suction Pressure has not changed at
start up. Cannot execute start-up
because suction pressure does not drop
in the time allotted. | Compressor miss-wired
Suction Pressure Sensor Failure (verify accuracy)
SOV bi-passing
Compressor not pumping |  | 
CL2.181.02 | Critical | PHS LOSS CO | Motor phase loss
protection | Compressor cable connection or motor
winding problem | Compressor cable connection or motor winding problem.
(Verify wiring and windings)
- Run drive diagnostics |  |