Skip to content

Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.175.00 fault code

Limp along mode

What the manual says

Limp along mode

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 9

CL2.175.00 | Major | LIMP MODE | Limp along mode | High or Low superheat detected for at
least 20 minutes. Limp Mode can also be
triggered by Loss of Sensor reading. Look
for Sensor Error. Limit Compressor
Speed to a constant value. | Possible refrigerant pressure or airflow problem
Sensor(s) faulted (out of range)
- Dome sensor
- Suction sensor
- Ambient sensor
- Indoor sensor (EEV in safe mode) |  | 
CL2.175.01 | Critical | LIMP MODE LO | Limp along mode | Loss of sensor reading. Compressor
operation is inhibited | Possible refrigerant pressure or airflow problem
Sensor(s) faulted (out of range)
- Dome sensor
- Suction sensor
- Ambient sensor
- Indoor sensor (EEV in safe mode) |  | 
CL2.176.00 | Critical | DRV COMM LO | Modbus comm failure | Loss of internal communication within
the Drive. | Loss of internal communication within the Drive.
On a persistent 176.00 error, the technician should cycle
power to the ODU. If error 176.00 returns, replace the
Drive.
**If replacement Drive has the same issue, investigate
for EMI and source. |  | 
CL2.177.00 | Normal | CUR DER | Drive current failure | Internal Derate is active due to high
Drive output current | High load conditions
- Refrigerant overcharge
- Dirty coil(s)
- low air flow
- recirculation
Compressor drive hardware failure
- Run drive diagnostics |  |