Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.175.00 fault code
Limp along mode
What the manual says
Limp along mode
Source
Trane Alert Codes (ComfortLink II Alarm ID list), p. 9
CL2.175.00 | Major | LIMP MODE | Limp along mode | High or Low superheat detected for at least 20 minutes. Limp Mode can also be triggered by Loss of Sensor reading. Look for Sensor Error. Limit Compressor Speed to a constant value. | Possible refrigerant pressure or airflow problem Sensor(s) faulted (out of range) - Dome sensor - Suction sensor - Ambient sensor - Indoor sensor (EEV in safe mode) | | CL2.175.01 | Critical | LIMP MODE LO | Limp along mode | Loss of sensor reading. Compressor operation is inhibited | Possible refrigerant pressure or airflow problem Sensor(s) faulted (out of range) - Dome sensor - Suction sensor - Ambient sensor - Indoor sensor (EEV in safe mode) | | CL2.176.00 | Critical | DRV COMM LO | Modbus comm failure | Loss of internal communication within the Drive. | Loss of internal communication within the Drive. On a persistent 176.00 error, the technician should cycle power to the ODU. If error 176.00 returns, replace the Drive. **If replacement Drive has the same issue, investigate for EMI and source. | | CL2.177.00 | Normal | CUR DER | Drive current failure | Internal Derate is active due to high Drive output current | High load conditions - Refrigerant overcharge - Dirty coil(s) - low air flow - recirculation Compressor drive hardware failure - Run drive diagnostics | |
Ask about your unit
Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).