Outdoor EEV error

What the manual says

Outdoor EEV error

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 9

CL2.164.02 | Normal | EEV OPEN ERR | Outdoor EEV error | EEV migrated to open position but
superheat is not at the desired set point.
Valve is not responding to a change in
position. | Possible stuck valve (EEV)
ET or GT sensor is out of calibration
Low refrigerant charge |  | 
CL2.164.03 | Normal | EEV CLSE ERR | Outdoor EEV error | EEV migrated to closed position but
superheat is not at the desired set point.
Valve is not responding to a change in
position. | Possible stuck valve (EEV)
ET or GT sensor is out of calibration |  | 
CL2.165.01 | Normal | LO SUPERHEAT | Low superheat
occurrences | Low superheat (less than 3 degrees)has
been detected for more than 60 minutes | Possible stuck valve (EEV)
ET or GT sensor is out of calibration
Low air flow
Refrigerant overcharge
Check valve leaking |  | 
CL2.166.00 | Major | SYSTEM4 ERR | Indoor EEV error | EEV motor is at the closed position and
the superheat is less than 3 degrees.
**Five consecutive cycles with low
superheat will result in a system lockout.
Cycle power to reset | Possible stuck valve (EEV)
ET or GT sensor is out of calibration
Check valve leaking (Not all models have external check
valve)
Restricted ET refrigeration circuit |  | 
CL2.166.01 | Normal | LO SUPERHEAT | Low superheat
occurrences | EEV valve closed and still flooding | Possible stuck valve (EEV)
ET or GT sensor is out of calibration
Low air flow
Refrigerant overcharge
Check valve leaking |  | 
CL2.167.00 | Major | OD DATA MISS | EVC missing OD