Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.153.00 fault code
Cycling limit open
What the manual says
Cycling limit open
Source
Trane Alert Codes (ComfortLink II Alarm ID list), p. 8
CL2.153.00 | Major | EH CTCO TRIP | Cycling limit open | The EHC has detected that the CTCO has tripped 6 times within the same heating cycle | Check for low airflow caused by restricted return air, dirty filter, blower wheel, or coil | | CL2.153.01 | Normal | EH CTCO TRIP | Cycling limit open | The EHC has detected that the CTCO has tripped with no airflow demand | Check for low airflow caused by restricted return air, dirty filter, blower wheel, or coil **Cycle power to the air handler to clear the alert. | | CL2.154.00 | Critical | EH OFF/NO AF | No airflow/low airflow for electric heat | The EHC has been locked out because the minimum airflow request has not been met | Controls prior to CNT06726 and CNT07015. Cycle power to the system. If alert does not clear, contact your FSR. Controls CNT06726, CNT07015, and later. Minimum 60%- 70% airflow for electric heat cannot be met. Verify external static pressure/airflow table and compare to minimum airflow listed in Service Facts. | | CL2.154.01 | Major | EH LIM/NO AF | Low airflow is limiting electric heat stages | The EHC is limiting the amount of electric heat due to inadequate airflow | Controls prior to CNT06726 and CNT07015. Cycle power to the system. If alert does not clear, contact your FSR. Controls CNT06726, CNT07015, and later. Minimum 60%- 70% airflow for electric heat cannot be met. Verify external static pressure/airflow table and compare to minimum airflow listed in Service Facts. | | CL2.155.00 | Major | EEV MTR ERR | EEV Motor Fault | The indoor EEV motor fault has been detected for 8 consecutive times | EEV motor windings or the connecting harness are bad **Verify that motor resistance matches Service Facts literature | | CL2.155.01 | Major | EEV MTR ERR | EEV Motor Fault | The indoor EEV motor winding has been detected to be open or shorted | EEV motor windings or the harness are bad | | CL2.155.02 | Major | EEV MTR ERR | EEV Motor Fault | The OD EEV electric coil has an open or intermittent short circuit. | EEV motor coil open or shorted | | CL2.156.00 | Major | SYSTEM1 ERR | High superheat
Ask about your unit
Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).
Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.