What the manual says

Cycling limit open

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 8

CL2.153.00 | Major | EH CTCO TRIP | Cycling limit open | The EHC has detected that the CTCO
has tripped 6 times within the same
heating cycle | Check for low airflow caused by restricted return air, dirty
filter, blower wheel, or coil |  | 
CL2.153.01 | Normal | EH CTCO TRIP | Cycling limit open | The EHC has detected that the CTCO
has tripped with no airflow demand | Check for low airflow caused by restricted return air, dirty
filter, blower wheel, or coil
**Cycle power to the air handler to clear the alert. |  | 
CL2.154.00 | Critical | EH OFF/NO AF | No airflow/low
airflow for
electric heat | The EHC has been locked out because
the minimum airflow request has not
been met | Controls prior to CNT06726 and CNT07015. Cycle power
to the system. If alert does not clear, contact your FSR.
Controls CNT06726, CNT07015, and later. Minimum 60%-
70% airflow for electric heat cannot be met. Verify external
static pressure/airflow table and compare to minimum
airflow listed in Service Facts. |  | 
CL2.154.01 | Major | EH LIM/NO AF | Low airflow is
limiting electric
heat stages | The EHC is limiting the amount of electric
heat due to inadequate airflow | Controls prior to CNT06726 and CNT07015. Cycle power
to the system. If alert does not clear, contact your FSR.
Controls CNT06726, CNT07015, and later. Minimum 60%-
70% airflow for electric heat cannot be met. Verify external
static pressure/airflow table and compare to minimum
airflow listed in Service Facts. |  | 
CL2.155.00 | Major | EEV MTR ERR | EEV Motor Fault | The indoor EEV motor fault has been
detected for 8 consecutive times | EEV motor windings or the connecting harness are bad
**Verify that motor resistance matches Service Facts
literature |  | 
CL2.155.01 | Major | EEV MTR ERR | EEV Motor Fault | The indoor EEV motor winding has been
detected to be open or shorted | EEV motor windings or the harness are bad |  | 
CL2.155.02 | Major | EEV MTR ERR | EEV Motor Fault | The OD EEV electric coil has an open or
intermittent short circuit. | EEV motor coil open or shorted |  | 
CL2.156.00 | Major | SYSTEM1 ERR | High superheat
Ask about your unit

Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.