Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.101.00 fault code

Y1 Off Error

What the manual says

Y1 Off Error

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 5

CL2.101.00 | Major | Y1 Off Err | Y1 Off Error | Y1 relay on indoor unit control board is
“OFF” with a call for cooling
**If comfort control is setup for single
stage cooling and a communicating
outdoor unit is not discovered on the
communicating bus, the Y1 relay on the
indoor control board will apply 24v to Y1
terminal on a active call for cooling | Internal control failure
**Replace control board |  | 
CL2.101.01 | Major | Y1 On Err | Y1 On Error | Y1 relay on indoor unit control board is
“ON” without a call for cooling
**If comfort control is setup for single
stage cooling and a communicating
outdoor unit is not discovered on the
communicating bus, the Y1 relay on the
indoor control board will apply 24v to Y1
terminal on a active call for cooling | 24 volts sensed on Y1 terminal of low voltage terminal
board without an active call for cooling
24 volts applied to Y1 terminal when a communicating
outdoor unit is installed
Onboard Y1 relay stuck closed
**Replace control board |  | 
CL2.102.00 | Major | Y2 No Y1 | Y2 No Y1 | 24 volts detected on Y2 without voltage
applied on Y1 | Y1 and Y2 field wiring reversed |  | 
CL2.104.00 | Normal | HT Off Err
EH RLY OPEN# | Heat Off Error
Electric heat
relay stuck open | Heat relay on control board is stuck open | Replace control board |  | 
CL2.104.01 | Normal | HT On Err
EH RLY WELD# | Heat On Error
Electric heat
relay stuck closed | Voltage is being sensed by onboard
sensing circuit when no voltage should be
Ask about your unit

Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.