Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.091.02 fault code
System Comm Error
What the manual says
System Comm Error
Source
Trane Alert Codes (ComfortLink II Alarm ID list), p. 5
CL2.091.02 | Critical | Sys Comm Err | System Comm Error | Loss of heat/cool demand **Heat/Cool demand is generated by comfort control every 1 minute and a fault is reported after 3 missed messages | Data line to comfort control broken or disconnected **0vDC measured between D & B at comfort control with ~12vDC measured at indoor unit Data (D) line and common (B) line reversed at outdoor unit **The Bit Master LED on indoor control board will be off, dim or flickering **0vDC will be measured with D & B wires connected at outdoor unit **12vDC will be measured on D & B field wires when disconnected from outdoor unit Data (D) line grounded going to outdoor unit **The Bit Master LED on indoor control board will be off, dim or flickering **0vDC will be measured with D & B wires connected at outdoor unit **0vDC will also be measured on D & B field wires when disconnected from outdoor unit If a communicating air cleaner is installed, remove (D) data wire and check to see if fault clears | |
Other Trane codes in this family
Ask about your unit
Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).
Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.