Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.090.00 fault code

Blower Comm CRC

What the manual says

Blower Comm CRC

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 4

CL2.090.00 | Normal | BLW COMM CRC | Blower Comm CRC | Blower motor unrecognized response
**Communication with blower motor
cannot be established | Reboot line voltage to indoor unit and check to see if fault
clears
**If error does not clear contact your local field rep for
additional support |  | 
CL2.090.01 | Normal | IND COMM CRC | Inducer Comm CRC | Inducer motor unrecognized response
**Communication with draft inducer
motor cannot be established | Reboot line voltage to furnace and check to see if fault
clears
**If error does not clear contact your local field rep for
additional support |  | 
CL2.090.02 | Normal | SYS COM ERR | System Comm
Error/CRC | Excessive communication errors
**Comfort control is continually
attempting to communicate with no idle
detected (bus busy) | R and B wiring reversed at comfort control or indoor unit
If a communicating air cleaner is installed, remove (D)
data wire and check to see if fault clears
**If error does not clear contact your local field rep for
additional support |  | 
CL2.091.00 | Critical | Blw Comm Err | Blower Comm Error | (CLII / AccuLink units only)
Loss of communication between serial
communicating blower motor and control
board
(3-Stage/Modulating Furnaces only)
Corrupted signal between integrated
furnace control board and inducer drive
control board can also cause this fault | No line voltage to blower motor or inducer motor control
board **Furnace 115vAC Air Handler 230vAC
Faulty low voltage connection between control board and
blower motor
**12vDC should be measured between 12v pin and GND
pin on control board and at terminals 1 & 4 at blower
motor low voltage plug
Perform 24volt “Go/No-Go Test” by applying 24vAC to
pins 3 & 4 at blower motor low voltage harness
**If motor runs replace control board if motor does not run
and motor harness tests good, replace motor assembly
(3-Stage/Modulating Furnace only) Disconnect 4-pin
connector from E9 on furnace control board, cycle power,
then test blower operation
**If blower runs, the inducer drive control board is causing
the fault |  | 
CL2.091.01 | Critical | Ind Comm Err | Inducer Comm Error | Loss of communication between furnace
control board and draft inducer motor
control board | Faulty connection or harness between furnace control
board and draft inducer motor control board
**On a call for heat the GREEN COM LED on the inducer
motor control board should be flashing to confirm
communication with furnace control board
Faulty inducer drive board |  |