Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.080.02 fault code
Reduced capacity
What the manual says
Reduced capacity
Source
Trane Alert Codes (ComfortLink II Alarm ID list), p. 4
CL2.080.02 | Normal | HP RPM REDUCED | Reduced capacity | High Pressure trip point has been exceeded and a 5 minute time out has been enforced. Restart is allowed but with reduced capacity. | Cooling Mode - Refrigerant overcharge - Outdoor fan failure - Outdoor airflow restriction Heating Mode - Refrigerant overcharge - Indoor blower failure - Indoor airflow restriction - Non-condensibles | | CL2.083.00 | Normal | Under Charge | | | | Obselete | CL2.083.01 | Normal | Over Charge | | | | Obselete | CL2.087.00 | Critical | Rollout Open | Rollout Open | Open flame rollout | Air impingement on burners or flame Draft inducer not operating properly Restricted heat exchanger Low outlet gas pressure | | CL2.087.01 | Critical | Rollout LO | | | | Obselete | CL2.088.00 | Normal | GND Fault | Ground Fault | Proper earth ground not detected (more than 8v line neutral to ground) | Furnace ground not connected to earth ground Chassis grounds not connected or poor connection Incoming power supply not grounded to main electrical
Ask about your unit
Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).
Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.