Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.080.02 fault code

Reduced capacity

What the manual says

Reduced capacity

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 4

CL2.080.02 | Normal | HP RPM REDUCED | Reduced capacity | High Pressure trip point has been
exceeded and a 5 minute time out has
been enforced. Restart is allowed but
with reduced capacity. | Cooling Mode
- Refrigerant overcharge
- Outdoor fan failure
- Outdoor airflow restriction
Heating Mode
- Refrigerant overcharge
- Indoor blower failure
- Indoor airflow restriction
- Non-condensibles |  | 
CL2.083.00 | Normal | Under Charge |  |  |  | Obselete | 
CL2.083.01 | Normal | Over Charge |  |  |  | Obselete | 
CL2.087.00 | Critical | Rollout Open | Rollout Open | Open flame rollout | Air impingement on burners or flame
Draft inducer not operating properly
Restricted heat exchanger
Low outlet gas pressure |  | 
CL2.087.01 | Critical | Rollout LO |  |  |  | Obselete | 
CL2.088.00 | Normal | GND Fault | Ground Fault | Proper earth ground not detected (more
than 8v line neutral to ground) | Furnace ground not connected to earth ground
Chassis grounds not connected or poor connection
Incoming power supply not grounded to main electrical
Ask about your unit

Last checked 2026-11-18 against Trane Alert Codes (ComfortLink II Alarm ID list).

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.