Trane Alert Codes (ComfortLink II Alarm ID list)Trane CL2.033.00 fault code

Polarity Error

What the manual says

Polarity Error

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 2

CL2.033.00 | Normal | Polarity Err | Polarity Error | Line voltage polarity reversed | Line hot (120v to ground) and line neutral (less than 10v
to ground) are reversed |  | 
CL2.034.00 | Critical | Flame Err | Flame Error | Flame sensed for more than 5 seconds
when no flame should be present | Gas valve will not close
**Debris in gas valve; no drip led installed
Internal failure of furnace control board
**Replace control board |  | 
CL2.037.00 | Normal | TIMERCONFLCT | Timer Conflict | Duplicate filter timers have been enabled | ISU 500 and/or 501 on the communicating comfort control
is not set to “E” for auto-discovery | Obselete | 
CL2.050.00 | Normal | DUP OD Temp |  | ????? | ????? | Obselete | 
CL2.052.00 | Normal | ICAS OPEN | ICAS OPEN | Indoor coil air sensor circuit open
**Sensor is used for defrost heat control.
The unit will divert to max control with a
sensor error | Sensor unplugged
Sensor open
Wiring harness open
Open = 3.3vDC at J10 on the AFC |  | 
CL2.052.01 | Normal | ICAS SHORT | ICAS SHORT | Indoor coil air sensor circuit shorted
**Sensor is used for defrost heat control.
The unit will divert to max control with a
sensor error | Sensor shorted
Wiring harness shorted
Shorted = 0vDC at J10 on the AFC |  | 
CL2.053.00 |  |  |  | Outdoor temperature sensor is open |  | Obselete | 
CL2.053.01 |  |  |  | Outdoor temperature sensor is shorted |  | Obselete | 
CL2.053.02 |  |  |  | Outdoor temperature sensor is not
reporting on the communication bus |  | Obselete | 
CL2.059.00 | Normal | AC Volts Low | AC Volts Low | Line voltage to furnace is too low (less
than 70vAC) | Improper voltage from main power supply
Faulty breaker or switch |  | 
CL2.059.01 | Normal | AC Volts Hi | AC Volts Hi | Line voltage to furnace is too high
(greater than 136vAC) | Improper voltage from main power supply |  | 
CL2.064.00 | Major | Button Stuck | Air Cleaner
Standby/On Button