Control Fault

What the manual says

Control Fault

Source

Trane Alert Codes (ComfortLink II Alarm ID list), p. 1

CL2.018.00 | Critical | Cntrl Fault | Control Fault | Internal control failure within indoor unit | Replace indoor control board.
**Board failure could be caused by line voltage spikes or
electrostatic discharge |  | 
CL2.018.01 | Critical |  |  |  |  | Obselete | 
CL2.018.02 | Major | AC Sns Err | AC Sensing Error | 24 volts not sensed at Y1 input of J1
connector on outdoor control board
**The Y1 input is monitored to sense very
short power interruptions that could
cause compressor short cycling | Faulty or missing “Y1” input into J1 connector on outdoor
control board
**Verify red wire to top center pin of J1 connector is
delivering 24vac to outdoor control board |  | 
CL2.018.03 | Major | Mem Fault | Control Fault | Internal control lockout within air cleaner | Re-power air cleaner; if fault does not clear replace the
power door. |  | 
CL2.018.04 | Critical | CTRL FLT | Control Fault | Internal control failure within outdoor unit | Replace outdoor control board (IVSC)
**Board failure could be caused by line voltage spikes or
electrostatic discharge |  | 
CL2.019.00 | Normal | Twin Error | Twin Error | Twinning Error | Furnaces with variable speed blowers cannot be twinned
Variable speed air handlers cannot be twinned |  | 
CL2.020.00 | Normal | Recycle | Recycle | Burners ignite and flame is proven then
flame drops out.
**After 10 recycles within the same call
for heat an ERR22 will be displayed on
the comfort control and RECYCLE LO
will be displayed on user interface | Gas valve solenoid failing
Inlet gas pressure dropping too low.
**Gas pressure regulator failing
**Debris in gas valve screen or blockage in supply line
Air impingement on burners or flame |  | 
CL2.020.01 | Normal | Retry | Retry | Flame sensor does not sense flame
**After 3 retries within the same call for
heat an ERR22 will be displayed on the
comfort control and RETRY LO will be
displayed on user interface | Flame sensor not sensing flame
**Less than 1 micro amp
Inlet gas pressure too low
Outlet gas pressure too low
Flame sensor not positioned properly in flame
Burner crossovers not aligned properly or restricted |  | 
CL2.022.00 | Critical | Recycle LO | Recycle Lockout | 10 burner recycles within a single call for
heat
**Burners
ignite and flame is proven then flame
drops out | Gas valve solenoid failing
Inlet gas pressure dropping too low.
**Gas pressure regulator failing
**Debris in gas valve screen or blockage in supply line
Air impingement on burners or flame |  | 
CL2.022.01 | Critical | Retry LO | Retry Lockout | 3 ignition attempts in a row without
proving flame within a single call for heat | Flame sensor not sensing flame
**Less than 1 micro amp
Inlet gas pressure too low
Outlet gas pressure too low
Flame sensor not positioned properly in flame
Burner crossovers not aligned properly or restricted |  |