410A Systems / Air Handlers / GAM5 / GAM5 Service FactsTrane 10 fault code

Low superheat (3)

What the manual says

Low superheat (3)

Source

410A Systems / Air Handlers / GAM5 / GAM5 Service Facts, p. 17

LED Color | EVC
Fault LED | Description | Possible Causes
RED | OFF | Standby | 
 | 1 | Stepper Motor coil has an open circuit or intermittent short | Faulty EEV motor / wiring harness
 | 2 | Control has detected an internal failure | Verify EEV motor resistance. EEV motor drive, motor
feedback, or 12v failure. Verify EEV motor resistance
 | 3 | Evaporator Temperature Sensor (ET) input out of range (Verify
resistance, 5VDC output from control) (1) | Sensor open / shorted, unplugged, wiring harness problem
 | 4 | Gas Temperature Sensor (GT) input out of range (Verify resistance,
5VDC output from control) (1) | Sensor open / shorted, unplugged, wiring harness problem
 | 5 | Stepper Motor Coil is shorted (2) | Faulty EEV motor / wiring harness
 | 6 | Valve is not responding to a change in position | Possible stuck valve, ET/GT sensor calibration
 | 7 | High superheat | System low on charge, liquid line restriction, ET/GT sensor
calibration
 | 10 | Low superheat (3) | Stuck valve, ET/GT sensor calibration, restricted
distributor line that ET is connected to, check valve leaking
 | 11 | Internal condensate drain switch activated for 100 seconds (2) | Condensate line clogged
 | 13 | Indoor frost protection activated (4) | Low / incorrect airflow, low refirgerant charge, ET sensor
calibration. Normal for low ambient cooling
 |  |  | 
 |  | 1) EEV will try to go to a safe position, cooling attempt allowed
2) EVC disables YO
3) Cooling attempt allowed, 5 consecutive Y calls with same condition disables YO
4) EVC disables YO for 5 minutes
NOTE: Faults 6, 7, & 10 may require jumper from "Test - Close" for 10 seconds to clear fault LED | 
NOTES: |  |  | 