MMLD018-048S6S, MMPD024-048S6S Outdoor Single Zone R-32 InstructionsLennox E665 fault code

External Contact Input ERROR

What the manual says

External Contact Input ERROR

Source

MMLD018-048S6S, MMPD024-048S6S Outdoor Single Zone R-32 Instructions, p. 53

No. | Error
Code | Meaning | Remarks
54 | E493 | FAN #1 motor output current error | 1. Change motor
2. Change INV PCB
55 | E496 | FAN #1 motor voltage sensor error | 1. Change motor
2. Change INV PCB
56 | E499 | FAN #1 IPM temperature sensor error | 1. Change motor
2. Change INV PCB
57 | E500 | IPM overheat error on inverter 1 | Check Outdoor Inverter PBA.
58 | E507 | Error due to high pressure switch open or compressor
down by high pressure | -
59 | E508 | Smart install is not installed | -
60 | E534 | Blockage detected on high pressure pipe during heating
operation. | 1. Check if the service valve is open
2. Check if there's any blockage on
the refrigerant cycle
(indoor unit/outdoor unit)
3. Check the EEV connection and
operation
4. Check if the connecting wire and
the pipe are OK
5. Check the compressor
61 | E554 | Gas leak detected | Check the refrigerant
62 | E556 | Error due to mismatching capacity of indoor and outdoor
unit | Check the indoor and outdoor unit
capacity
63 | E557 | DPM remote controller option error | Check the indoor option code
64 | E563 | Error due to mismatching indoor and outdoor unit | Check the outdoor EEPROM data
and indoor option code
65 | E590 | Inverter EEPROM Checksum error | -
66 | E594 | Fan EEPROM CheckSum error | 1. Check Fan EEPROM
67 | E601 | Communication error between wired remote control and
indoor unit | 1. Check remote control wire
connectors.
2. Change wired remote control.
68 | E665 | External Contact Input ERROR | 1. Check the External float switch
connection.
2. Check whether the drain has
been filled with water.
3. Check the emergency alarm
system (Emergency Stop)
69 | E695 | R-32 detection sensor life unpredictable error | 1. Check R-32 sensor.
2. Change R-32 sensor.