MMLD009S6S-1P / MMLD012S6S-1P / MMLD024S6S-1P / MMLD030S6S-1P / MMLD036S6S-1P / MMLD048S6S-1P / MMPD018S6S-1P / MMPD024S6S-1P / MMPD030S6S-1P / MMPD036S6S-1P / MMPD048S6S-1P seriesLennox E231 fault code

Outdoor temperature sensor error

What the manual says

Outdoor temperature sensor error

Models and series

Listed for: MMLD009S6S-1P, MMLD012S6S-1P, MMLD024S6S-1P, MMLD030S6S-1P, MMLD036S6S-1P, MMLD048S6S-1P, MMPD018S6S-1P, MMPD024S6S-1P, MMPD030S6S-1P, MMPD036S6S-1P, MMPD048S6S-1P.

Source

Lennox Powered by Samsung Mini-Split (HP) Service, p. 205

 | Error CODE | Description | 
 |  | Outdoor temperature sensor error | 
E221 Outdoor temperature sensor error
Power OFF
E231 Outdoor temperature sensor error
E251 Outdoor temperature sensor error
E320 Outdoor OLP sensor error
Is the temperature sensor connector No
Reconnect the temperature sensor connector.
connected?
Yes
Is the temperature
No Replace the temperature sensor. → Power on.
sensor measuring resistance similar to the table
→ Check the normal operation. → End the service.
on the left?
Ex) COND. sensor/outdoor unit temperature sensor
measuring resistance value by temperature: E231, E221
Current temp Current temp
Resistance (kΩ) Resistance (kΩ)
(°C) (°C)
70 4 20 10
60 5 10 20
50 6 0 30
40 7 -10 40
30 8
Ex) Room temperature: 26℃ - Resistance: 10.28KΩ
Ex) OLP sensor/discharge temperature sensor measuring
resistance value by temperature: E320, E251
Yes Current temp Current temp
Resistance (kΩ) Resistance (kΩ)
(°C) (°C)
80 40 30 180
70 50 20 220
60 60 10 320
50 90 0 550
40 110
Ex) Room temperature: 21℃- Resistance: 205.4KΩ
Does same error occur No
After checking normal operation, end the service.
again after power ON?
Yes
Replace the outdoor unit PCB. → Power ON
→ After confirming the state is normal, end the service. | E221 | Outdoor temperature sensor error | 
 | E231 | Outdoor temperature sensor error | 
 | E251 | Outdoor temperature sensor error | 
 | E320 | Outdoor OLP sensor error | 
Replace the outdoor unit PCB. → Power ON
→ After confirming the state is normal, end the service. |  |  | 