GD9T80 / GD9T96 / GR9T80 / GR9T96 seriesGoodman EEJ fault code (GD9T80 / GD9T96 / GR9T80 / GR9T96)

Inducer relay error.

What the manual says

Inducer relay error.

Models and series

Listed for: GD9T80, GD9T96, GR9T80, GR9T96.

Source

Service Manual RS6612301, p. 38

Symptom | LED
Status | Fault Description | Possible Causes | Corrective Action(s) | Notes & Cautions
Normal
furnace op­
eration with
weak flame
signal. | EE6 | Flame sense
micro amp signal
is low. | • Flame sensor is coated/
oxidized.
• Flame sensor incorrectly
positioned in burner flame.
• Lazy burner flame due to
improper gas pressure or
combution air. | • Clean flame sensor if
coated or oxidized.
• Inspect flame sensor
for proper alignment.
• Compare current gas
pressure to rating plate
and adjust as needed. | • Turn power OFF
prior to repair.
• Clean flame sensor
with steel wool.
• See “Vent/Flue
Pipe” section for
piping details.
• See rating plate for
proper gas pressure.
Furnace fails
to operate. | E10 | Grounding fault | • Poor neutral connection. | • Verify neutral wire
connection to furnace
and continuity to ground
source. | • Turn power OFF
prior to repair.
Furnace fails
to operate. | E11 | Open rollout
switch. | • Gas pressure too high.
• Burners mis-aligned.
• Restricted heat exchang­
er or venting. | • Check and correct gas
pressure.
• Check and correct
burner alignment.
• Check and correct
restriction | • Turn power OFF
prior to repair.
Furnace fails
to operate. | EEA | Polarity if 115 volt
AC is reversed. | • Polarity of 115 volt AC
power to furnace or inte­
grated control module is
reversed.
• Poor furnace ground. | • Review wiring diagram
to correct polarity.
• Verify proper ground.
Correct if necessary.
• Check and correct
wiring. | • Turn power OFF
prior to repair.
Furnace fails
to operate. | EEb | Gas valve is not
energized when it
should be.
External gas
valve error. | • Miswired gas valve
circuit.
• Open gas valve circuit.
• Gas valve relay on inte­
grated control board stuck
open. | • Check wiring in gas
valve circuit.
• Replace integrated con­
trol board. | • Turn power OFF
prior to repair.
Furnace fails
to operate. | EEC | Gas valve is
energized when it
should not be.
Internal gas valve
error. | • Miswired gas valve
circuit.
• Shorted gas valve wiring.
• Gas valve relay on inte­
grated control board stuck
open. | • Check wiring in gas
valve circuit.
• Replace integrated con­
trol board. | • Turn power OFF
prior to repair.
Furnace fails
to operate. | EEE | Internal Faults
or IRQ Loss in
integrated control
board. |  | • Replace integrated con­
trol board. | • Turn power OFF
prior to repair.
Twinning
feature not
working. | EEH | TWIN error. | • Both furnaces not on the
same 115 volt power from
breaker.
• Low voltage wiring error
or loose wiring connec­
tions. | • Verify 115 volt power to
each furnace.
• Check wiring connec­
tions.
• Replace integrated con­
trol board if necessary. | • Turn power OFF
prior to repair.
Furnace fails
to operate. | EEJ | Inducer relay
error. |  | • Replace integrated con­
trol board | • Turn power OFF
prior to repair.
• Replace the inte­
grated control board
with proper replace­
ment part.