GD9T80 / GD9T96 / GR9S96 / GR9T80 / GR9T96 / VR9S96 seriesGoodman EAL fault code (GD9T80 / GD9T96 / GR9S96 / GR9T80 / GR9T96 / VR9S96)

R-32 sensor has detected a refrigerant leak and furnace is in mitigation mode.

What the manual says

R-32 sensor has detected a refrigerant leak and furnace is in mitigation mode.

Models and series

Listed for: GD9T80, GD9T96, GR9S96, GR9T80, GR9T96, VR9S96.

Troubleshooting from the service manual

  1. 1. Display the A2L Refrigerant Leakage error code / (EAL).

    2. Shut down the gas operation. 3. Energize the optional ventilation and alarm outputs. 4. Run the fan at max CFM airflow.

    Service Manual RS6612301, p. 9

  2. Once “”YES”” is selected, the furnace will do the following: / 1) Display the A2L Refrigerant Leakage code (EAL)

    1) Display the A2L Refrigerant Leakage code (EAL) 2) Shut down the gas operation 3) Energize the optional ventilation and alarm outputs. 4) Run the fan at max CFM airflow The control will exit the verification function if: 1) The 5 minute timeout expires or 2) An alarm or fault is detected or 3) The user turns OFF the A2L Function Verification.”

    Service Manual RSD6612304, p. 7

Source

Service Manual RS6612301, p. 39

Symptom | LED
Status | Fault Description | Possible Causes | Corrective Action(s) | Notes & Cautions
Furnace
stops heat­
ing and only
the fan is
operating. | EAL | R-32 sensor
has detected a
refrigerant leak
and furnace is in
mitigation mode. |  | • Investigate the indoor coil for a refrig­
erant leak.
• Furnace will resume normal opera­
tion once a leak is no longer detected
and the 5-minute delay period is over. | • Turn power OFF
prior to repair.