CVA9, HVA9, TVA9, CVH8, HVH8, TVH8 R-410A Variable-Speed Split System Air Conditioner & Heat Pump Service ManualComfortmaker 99 fault code

HIGH TORQUE LOCKOUT (Elevated from fault code 98 when 98 occurs at lowest stage)

What the manual says

HIGH TORQUE LOCKOUT (Elevated from fault code 98 when 98 occurs at lowest stage)

Checks from the manual

  1. HIGH TORQUE LOCKOUT (Elevated from fault code 98 when 98 occurs at lowest stage) | 2 hours | Cool | Overcharged System | Check system subcooling to determine charge status, if high remove charge using Charging Mode (follow proper charging procedures) | | | | Heat | Overcharged System | Check charge in heating mode per heating check charge chart. If pressures do not match then pull out charge, weigh in using heating charge method | | | | Both | Mis-wire | Check mis-wire of compressor leads at terminals U,V,W | | | | Both | Outdoor Airflow too low or off | Check ODU coil for clogging (ice or debris) and clean if necessary; Troubleshoot ODU fan motor and make sure it is working | | | | Both | Expansion Device Restriction | Troubleshoot TXV | | | | | | Troubleshoot EXV | | | | Heat | Overcharged System | Check charge in heating mode per heating check charge chart. If pressures do not match then pull out charge, weigh in using heating charge method

Source

CVA9, HVA9, TVA9, CVH8, HVH8, TVH8 R-410A Variable-Speed Split System Air Conditioner & Heat Pump Service Manual, p. 23

99 | System
Malfunction | HIGH TORQUE
LOCKOUT
(Elevated from fault
code 98 when 98
occurs at lowest stage) | 2 hours | Cool | Overcharged System | Check system subcooling to determine charge
status, if high remove charge using Charging Mode
(follow proper charging procedures)
 |  |  |  | Heat | Overcharged System | Check charge in heating mode per heating check
charge chart. If pressures do not match then pull
out charge, weigh in using heating charge method
 |  |  |  | Both | Mis-wire | Check mis-wire of compressor leads at
terminals U,V,W
 |  |  |  | Both | Outdoor Airflow too low
or off | Check ODU coil for clogging (ice or debris) and
clean if necessary; Troubleshoot ODU fan motor
and make sure it is working
 |  |  |  | Both | Expansion Device
Restriction | Troubleshoot TXV
 |  |  |  |  |  | Troubleshoot EXV
 |  |  |  | Heat | Overcharged System | Check charge in heating mode per heating check
charge chart. If pressures do not match then pull
out charge, weigh in using heating charge method