CVA9, HVA9, TVA9, CVH8, HVH8, TVH8 R-410A Variable-Speed Split System Air Conditioner & Heat Pump Service ManualComfortmaker 88 fault code

COMPRESSOR / INVERTER LOCKOUT (Elevated from fault code 79 after 5 occurrences)

What the manual says

COMPRESSOR / INVERTER LOCKOUT (Elevated from fault code 79 after 5 occurrences)

Checks from the manual

  1. COMPRESSOR / INVERTER LOCKOUT (Elevated from fault code 79 after 5 occurrences) | 2 Hours | Both | Blocked Inverter Heat Exchanger (fins) | Check Inverter fins for debris and clean if necessary | | | | | Condenser Airflow too low or off | Check Condenser (IDU in heating, ODU in cooling) for clogging (ice or debris) and clean if necessary; Troubleshoot fan motor and make sure it is working | | | | | Evaporator Airflow too low or off | Check Evaporator (IDU in cooling, ODU in heating) for clogging (ice or debris) and clean if necessary; Troubleshoot fan motor and make sure it is working | | | | | High Load conditions at cold ambient heating or high ambient cooling | Over charge: Check system charge | | | | | Inverter damage | Replace inverter

Source

CVA9, HVA9, TVA9, CVH8, HVH8, TVH8 R-410A Variable-Speed Split System Air Conditioner & Heat Pump Service Manual, p. 22

88 | System
Malfunction | COMPRESSOR /
INVERTER LOCKOUT
(Elevated from fault code
79 after 5 occurrences) | 2 Hours | Both | Blocked Inverter Heat
Exchanger (fins) | Check Inverter fins for debris and clean if
necessary
 |  |  |  |  | Condenser Airflow too
low or off | Check Condenser (IDU in heating, ODU in cooling)
for clogging (ice or debris) and clean if necessary;
Troubleshoot fan motor and make sure it is working
 |  |  |  |  | Evaporator Airflow too
low or off | Check Evaporator (IDU in cooling, ODU in heating)
for clogging (ice or debris) and clean if necessary;
Troubleshoot fan motor and make sure it is working
 |  |  |  |  | High Load conditions at
cold ambient heating or
high ambient cooling | Over charge: Check system charge
 |  |  |  |  | Inverter damage | Replace inverter