Skip to content

ERV & HRV Fresh Air Systems User and Installer ManualCarrier E01 fault code

Supply damper range

What the manual says

Supply damper range

Checks from the manual

  1. STEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may have to be removed to access the damper system). Plug in the unit.
  2. If STEP 1 did not fix the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any loose wires.
  3. If STEP 2 did not fix the problem, perform STEP 3: If the damper is not moving at all, unplug J7 (red) from the electronic assembly, connect the white damper system connector into J7. If the damper moves (but the system still shows an error), the electronic assembly must be replaced. Otherwise, replace the damper system.

Source

ERV & HRV Fresh Air Systems User and Installer Manual, p. 18

E01 | Supply damper range | STEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may
have to be removed to access the damper system). Plug in the unit.
If STEP 1 did not fix the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white)
is well inserted, check for any loose wires.
If STEP 2 did not fix the problem, perform STEP 3: If the damper is not moving at all, unplug J7 (red) from the
electronic assembly, connect the white damper system connector into J7. If the damper moves (but the system
still shows an error), the electronic assembly must be replaced.
Otherwise, replace the damper system.
Ask about your unit

Last checked 2026-10-18 against ERV & HRV Fresh Air Systems User and Installer Manual.

Safety: disconnect power before opening the unit. Gas, high voltage and refrigerant work belongs to a licensed technician.

No card

Start free — 14 days