RESI-GF-A93DF1EK-92G1DFEK-DOWNFLOW-INSTALLATIONMANUALArmstrong Air E273 fault code

Soft lockout - Exceeded maximum number of recycles. Last recycle due to flame failure.

What the manual says

Soft lockout - Exceeded maximum number of recycles. Last recycle due to flame failure.

Checks from the manual

  1. Check micro-amperes of flame sensor using control diagnostics or field-installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground. Clears when heat call finishes successfully.

Source

RESI-GF-A93DF1EK-92G1DFEK-DOWNFLOW-INSTALLATIONMANUAL, p. 44

E273 | Soft lockout - Exceeded maximum number of
recycles. Last recycle due to flame failure. | Check micro-amperes of flame sensor using control diagnostics or
field-installed mode. Clean or replace sensor. Measure voltage of
neutral to ground to ensure good unit ground. Clears when heat call
finishes successfully.